Three long-rod silicone rubber composite insulators used in 230kV power transmission lines were evaluated for aging affects.
The insulators were obtained from various outdoor desert locations within Saudi Arabia where they had been in service for
6years. Surface degradation associated with the aging process was analyzed by using Scanning Electron Microscopy (SEM) coupled
with Energy Dispersive X-ray Spectroscopy (EDS), Fourier Transform Infra-Red Spectroscopy (FTIR), and Electron Spectroscopy
for Chemical Analysis (ESCA). Electrical performance of insulators was evaluated by Rapid Flashover Voltage Tests (RFVT) and
Pollution Severity Measurement Tests. Depending on their locations of service, the samples exhibited various types of pollutants
at their surfaces. The analysis indicated that the insulator material showed localized surface degradation while there was
no evidence of micro-cracking. Furthermore, it was noted that the electrical performance of the insulators was not significantly
affected by exposure during the in-service period.